Orion – ONL 10-40K 31 (DC220)

Offer limits

Category:

Key Features

 Galvanic isolation design to withstand all kinds of load

• Fully coating PCBAs to withstand harsh environment

 Unique ventilation design for effective heat dissipation

• Emergency power off function (EPO)

• Wide input voltage and frequency range to withstand robust

environment

• High short-circuit and overload capabilities

• Built-in Maintenance bypass switch

• ECO mode operation for energy saving(ECO)

Specifications

       MODEL ONL-10K/31-DC220 ONL-15K/31-DC220 ONL-20K/31-DC220 ONL-30K/31-DC220 ONL-40K/31-DC220
           Phase 3-phase in / 1-phase out
           Capacity 10KVA/8KW 15KVA/12KW 20KVA/16KW 30KVA/24KW 40KVA/32KW
          INPUT
           Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
           Acceptable Voltage Range 285VAC ~ 475VAC
           Frequency 50/60 Hz ± 10%
          INVERTER
           Nominal Voltage 208VAC/220VAC/230VAC/240VAC (Selectable)
           Precision Stationary: ±1%;  Transitory: ±5% (load variations 100-0-100%)
           Frequency 50/60 Hz synchronised ±1%;  With mains absent ±0.1Hz
           Max. Synchronisation Speed ±1 Hz/s
           Waveform Pure Sinewave
        Total Harmonic Distortion

(THDv)

<2% (Linear Load);  <5% (Non-linear Load)
           Phase Displacement 120º ±1% (balanced load);  120º ±2% (imbalances 50% of the load)
           Dynamic Recovery Time 3 cycles at 90 % of the static value
           Admissible Overload 110% for 10min; 150% for 60sec ; >160% for 200ms
           Admissible Crest Factor 3:1
           Admissible Power Factor 0.6~1 (inductive or capacitive)
        Imbalance Output Voltage

@ 100% Unbalanced Load

<1%
           Current Limit High overload, short-circuit:  RMS Voltage Limit

High Crest-Factor current:  Peak Voltage Limit

          STATIC BYPASS
           Type Solid state
           Voltage 220V ±25%
           Frequency 50/60 Hz
           Activation Criterion Microprocessor control
           Transfer Time Zero
           Admissible Overload 150% for 1 hour;  180% for 30sec;  >200% for 200ms
           Transfer to Bypass Immediate,  for overloads above 160%
           Retransfer Automatic after alarm clear
          MAINTENANCE BYPASS
           Type Without interruption
           Voltage 220V ±25%
           Frequency 50/60 Hz
           Overall Efficiency Line Mode 90% 90% 91% 92%
Battery Mode 90% 90% 91% 93%
          BATTERY & CHARGER
           Battery Type and Numbers 12VDC x 16 pcs (16/18 pcs adjustable)
           Nominal Battery Voltage 192 VDC (Based on 16 pcs batteries)
           Charging Method CC/CV
           Charging Current Default 10A,  Max. = Capacity / Battery Voltage,  Max. 40A
          PHYSICAL
           Dimensions, D x W x H(mm) 656 x 405 x 817 656 x 405 x 941 821 x 432 x 1159
           Net Weight (Kgs) 118 120 145 193 278